Table of Contents
- Humidity instruments and their real accuracy
- How to measure humidity in rooms, cabinets and warehouses
- How to calibrate a hygrometer with salt
- How capacitive and resistive sensors differ
- Relative humidity and dew point: why reading RH is not enough
- Humidity indicator cards (HIC): how to read them correctly
- Measuring humidity inside cartons and containers
- Reading the result and acting on it
- Frequently asked questions
- What is the dew point and why does it matter?
- How do you read a humidity indicator card?
- What is the difference between capacitive and resistive hygrometers?
- How do you measure humidity in a room?
- Which type of hygrometer is accurate?
- How do you know if a hygrometer is correct?
- How much does a hygrometer cost?
- How do you measure humidity in a wardrobe?
- Contact ICD Vietnam for advice on desiccant packets
- References
- Related articles
Reviewed and updated by ICD - Week 47/2026
To measure humidity reliably, put an electronic hygrometer in the middle of the space, wait until the reading settles, then check it against table salt: a saturated salt solution holds the air at about 75% RH (75.3% at 25 °C). Household hygrometers are often off by several points of RH, so treat the number as a guide, not an absolute.
This guide covers the instruments and their real accuracy, where to place them, how to calibrate with salt, why you should read the dew point as well, how to read a humidity indicator card and how to measure inside cartons and containers. The EPA notes that a meter reading both temperature and humidity usually costs under 50 USD, so price is not the question. The real questions are where you measure, how far you can trust the number and how you check it.
Humidity instruments and their real accuracy
Every hygrometer gives a reading inside a margin of error. The Collections Trust (UK) museum monitoring guide states that a relative humidity meter only tells you the true value to within a few percent, and two units that both read correctly to a “±3%” specification can still differ from each other by up to 6%. The UK National Physical Laboratory (NPL) adds in its humidity good practice guide that under ideal conditions RH can be measured to about ±2 to ±3% RH, and under difficult conditions to ±5 to ±10% RH or worse.
| Instrument | Typical error | Advantages | Limitations | Best for |
|---|---|---|---|---|
| Handheld or logging electronic hygrometer | ±2% (Collections Trust) | Direct reading, with temperature | Needs time to settle; sensor drifts, periodic checks needed | Rooms, warehouses, cabinets, boxes |
| Dial hygrometer (hair or metal strip) | ±5% when new and just calibrated; cheap models drift much further | Cheap, no battery | Loses accuracy when moved; needs a monthly check | Rough reference only |
| Sling psychrometer (wet and dry bulb) | ±2% if read correctly | Instant reading, no electronic sensor | Needs technique and a lookup table; reader error | Use as a comparison standard |
| Humidity indicator card (HIC) | Shows only whether a printed threshold has been passed | Stick it inside a carton and read it at a glance | Less accurate than the instruments above; no continuous reading | Sealed cartons, boxes, packaging |
| Data logger | Depends on the model, typically about ±2 to ±3% RH | Gives an hourly history | Costly; many models cannot take prolonged high humidity | Containers, warehouses, high-value cargo |
The independent test data worth looking at comes from the German Mold Remediation Association (BSS). It tested 8 electronic hygrometers priced from 5.99 to 136 euros and 6 dial hygrometers against a reference instrument calibrated at a testing institute. Every electronic hygrometer was acceptable, including the cheapest (off by 4.4% RH); the best was off by only 0.5% RH. By contrast, three dial hygrometers of the same make and model differed from each other by up to 12% RH. The test ran in 2015 to 2016 so the models have changed, but its conclusion still holds: an electronic hygrometer is fine for the home, and a dial hygrometer should not be trusted.
Large rooms and warehouses bring another limit. Brown (1994) points out that a single RH reading in a large space is hard to justify unless temperature and water vapor content there have been shown to be uniform. To know a whole warehouse, you need several measuring points.
How to measure humidity in rooms, cabinets and warehouses
Put the hygrometer in the middle of the space, away from windows, air conditioners, stoves, heat sources and sunlight, because those spots create a local microclimate that differs sharply from the rest of the room. When you first place it or move it to another room, wait for the reading to settle: the Collections Trust notes that a handheld electronic hygrometer can take up to half an hour to stabilize.
Humidity changes by the hour and by room, so do not settle on a single reading. Measure in the morning, afternoon and evening and record the temperature too, because RH without temperature does not let you work out the dew point (next section). The most practical method is to put two hygrometers of different brands side by side for a day: if the two differ by more than their stated specification, one of them has drifted.
How to calibrate a hygrometer with salt
A saturated salt solution in a sealed container holds the relative humidity above the solution at a fixed value for each temperature, which is why it has long been used to check hygrometers. Greenspan (US National Bureau of Standards, 1977) published a table of reference values and uncertainties; the two points used most often at room temperature are in the table below.
| Saturated salt | 20 °C | 25 °C | 30 °C | Used to check |
|---|---|---|---|---|
| Magnesium chloride (MgCl₂) | 33.1 ± 0.2% | 32.8 ± 0.2% | 32.4 ± 0.1% | Low end of the working range |
| Sodium chloride (table salt, NaCl) | 75.5 ± 0.1% | 75.3 ± 0.1% | 75.1 ± 0.1% | High end, easy to do at home |
Steps at home with table salt, following the principle in Greenspan’s paper:
- Mix table salt with a few drops of distilled water into a thick slurry with undissolved salt left over; do not make a thin brine, because then the RH will read above 75%.
- Put the salt slurry in a bottle cap and place it with the hygrometer in a small sealed box; the hygrometer must not touch the salt, and the box must not sit in the sun or in an air conditioner draft.
- Keep the temperature steady and wait until the reading stops changing, which usually takes anywhere from a few hours to a day depending on the box and the meter.
- Read it as soon as you open the box, compare it with the table value for the actual room temperature, and record the offset.
For a more reliable two-point check, set up a second box with magnesium chloride, because a meter can be right at 75% yet off at 33%. I recommend recording the offset and adding or subtracting it when you read, rather than adjusting the meter: the Collections Trust warns that adjusting the device makes it fail sooner and can cause more drift, so many institutions only record the offset and apply a correction factor.
How often to check: NPL suggests calibrating a humidity meter roughly every 6 to 12 months (more often under harsh use); the Collections Trust recommends a salt check every 6 months for handheld electronic hygrometers and every month for dial hygrometers. Vaisala analyzed about 5,000 calibrations of 2,000 probes and found that most were still within the published accuracy after two years, with an estimated drift of ±0.5% RH per year to use in uncertainty calculations; those are industrial probes, so household meters should be checked more often.
How capacitive and resistive sensors differ
Electronic hygrometers use one of two principles: a capacitive sensor measures the change in the dielectric constant of a polymer layer as it absorbs moisture, while a resistive sensor measures the change in resistance of a moisture-absorbing material. The comparison of humidity sensing technologies from UC Davis shows that the polymer capacitive type drifts about 0.5% RH per year and responds in 4 to 60 seconds, while the polymer resistive type drifts under 2% per year but responds more slowly, in about 2 minutes. These are figures for the individual devices listed, not general specifications for every meter on the market.
What the two types have in common is that the sensing material is always exposed to the air, so it is affected by dust, volatile chemicals such as paint or solvents, and excessive heat or humidity. Condensation directly on the sensor and leaving the meter for long periods in near-saturated air are the two fastest ways to throw it off; after that, check it with salt before trusting its readings again.
Relative humidity and dew point: why reading RH is not enough
Relative humidity (RH) is the ratio between the water vapor present and the maximum amount the air can hold at that temperature. Because the maximum rises steeply with temperature, the same amount of water vapor gives a different RH when the temperature changes: a room at 70% RH during the day can climb close to 100% as it cools at night, even though the water vapor has not increased.
The dew point is the temperature at which the air becomes saturated (100% RH) and water vapor starts to condense into water. Any surface colder than the dew point gets wet. The Magnus formula with coefficients a = 17.625 and b = 243.04 °C (the form used in Lawrence, 2005) gives the values in the table below; the last column is Lawrence’s own rule of thumb: the dew point falls about 1 °C for every 5% RH below 100%. That rule is accurate to within 1 °C for 0 to 30 °C and RH above 50%, and does not apply at lower RH.
| Temperature | RH | Dew point by formula | Rule of thumb 1 °C / 5% | Meaning |
|---|---|---|---|---|
| 30 °C | 90% | About 28.2 °C | 28.0 °C | A wall below 28 °C gets wet immediately |
| 30 °C | 70% | About 23.9 °C | 24.0 °C | A surface below 23.9 °C will get wet |
| 25 °C | 60% | About 16.7 °C | 17.0 °C | A 15 °C cold pipe will get wet |
| 30 °C | 50% | About 18.4 °C | 20.0 °C (close to the threshold, 1.6 °C off) | Lower risk, but still present on cold surfaces |
| 25 °C | 40% | About 10.5 °C | Not applicable (RH below 50%) | Very little risk of condensation |
That is why a hygrometer that also shows temperature is so useful. Take a container loaded at 30 °C and 75% RH: its dew point is about 25.1 °C. When the ship crosses cold seas and the steel walls fall below that level, water vapor condenses on the walls and roof even though the average RH inside the container sounds acceptable. That is the mechanism behind container sweat.
Humidity indicator cards (HIC): how to read them correctly
The card has spots of chemical that change color from blue (dry) to pink (humid) when RH rises above the threshold printed beside the spot; a pale purple (lavender) spot means the RH is exactly at that spot’s threshold. To read it, find the spot whose color is closest to the comparison band printed on the card; the humidity is the percentage printed next to that spot. Card makers state that the spots change color within 8 hours of a humidity change, and a reversible card turns blue again when the air dries, so the card shows recent conditions, not the instant value. The Collections Trust places cards among the cheap indicators, less accurate than the instruments above, suitable inside boxes or display cases.
In semiconductor component packaging, the IPC/JEDEC J-STD-033C standard puts the card together with a desiccant packet inside a moisture barrier bag. The points worth remembering from that standard: read the card as soon as you take it out of the bag, at 23 ± 5 °C for best accuracy; do not place the card under the desiccant packet; if the 10% spot is already pink when you open the bag, the moisture-sensitive components have gone past their allowed exposure and must be baked by the proper procedure; and a card that has reached its 60% mark (60% spot pink) is no longer accurate and must be discarded. The 5, 10 and 60% set of spots comes from that standard; ordinary goods more often use a 10, 20, 30, 40% set.
Measuring humidity inside cartons and containers
Three methods are commonly used: an indicator card placed next to a desiccant packet, to be read when the carton is opened; a data logger recording temperature and RH throughout the journey; and an electronic hygrometer mounted in the middle of a warehouse for a daily log. For sea freight, a hygrometer hanging at one point does not represent the whole container, because moisture is distributed unevenly between the roof, the door and the walls (the same reason Brown gives above for large rooms).

A practical approach: place a data logger or indicator card in at least two positions, near the door and deep inside, record temperature as well so you can calculate the dew point, and compare the readings when the container is opened. When choosing a logger, mind its limits: the US National Park Service (NPS) guide notes that none of the units in its comparison are meant for outdoor use or prolonged high humidity, and some perform poorly below 20% RH; read the working range in the specification, not just the accuracy figure. For the desiccant dose for each journey, see how to use desiccant packets correctly.
Reading the result and acting on it
The EPA recommends keeping indoor humidity below 60%, ideally 30 to 50%. Above 60% is the zone where mold can grow, so look for the moisture source, ventilate and dehumidify; below 30% is dry and usually calls for humidifying occupied rooms. When you use desiccant packets in a cabinet, box or carton, place a small hygrometer or indicator card next to the packet to see the real humidity; if the reading does not fall after a few days, the packet is too small for the volume or the packaging is not airtight (our inference, which you should confirm by testing).
For target levels, see what indoor humidity is good and safe humidity for storing goods. The packet dose formula is in the desiccant packet guide mentioned above. ICD Vietnam supplies industrial desiccant beads, bags and sheets in the ICD desiccant category.

Frequently asked questions
What is the dew point and why does it matter?
It is the temperature at which air becomes saturated and water vapor starts to condense. Any surface colder than the dew point gets wet; for example, 30 °C and 70% RH has a dew point of about 23.9 °C.
How do you read a humidity indicator card?
Find the spot whose color is closest to the comparison band printed on the card; blue means dry, pink means humid, and pale purple (lavender) means RH is exactly at that spot’s threshold. Read it as soon as you open the bag, at about 23 °C for best accuracy.
What is the difference between capacitive and resistive hygrometers?
Capacitive sensors measure the change in the dielectric constant of a polymer layer, while resistive sensors measure the change in resistance of the moisture-absorbing layer. According to the UC Davis comparison table, the polymer capacitive type drifts about 0.5% RH per year and the polymer resistive type under 2% and responds more slowly; those are figures for the individual devices listed.
How do you measure humidity in a room?
Put an electronic hygrometer in the middle of the room, away from windows, air conditioners and heat sources; wait for the reading to settle (it can take up to half an hour), then read it, and measure at several times of day.
Which type of hygrometer is accurate?
The Collections Trust gives ±2% for a handheld electronic hygrometer and ±5% for a hair-type dial hygrometer. The BSS test found every electronic hygrometer off by at most 4.4% RH, while three dial hygrometers of the same make differed from each other by up to 12%.
How do you know if a hygrometer is correct?
Do the salt test: put the hygrometer with a saturated table salt slurry in a sealed box, wait for the reading to settle, then compare it with about 75% RH (75.3% at 25 °C). For more certainty, add a 33% check with magnesium chloride.
How much does a hygrometer cost?
The EPA notes that a meter reading both temperature and humidity usually costs under 50 USD in a hardware store. Prices in Vietnam vary by type.
How do you measure humidity in a wardrobe?
Put a small hygrometer in the wardrobe, close the door for about half an hour, then read it. The EPA recommends staying below 60%, ideally 30 to 50%.
Contact ICD Vietnam for advice on desiccant packets
ICD Vietnam Industrial Production Co., Ltd.
Northern Vietnam: 3rd Floor, Thang Long A1 Building, Bau Hamlet, Thien Loc Commune, Hanoi - 0983 797 186 / 090 345 9186 / 090 5859 186
Southern Vietnam: 551/212 Le Van Khuong Street, Tan Thoi Hiep Ward, District 12, Ho Chi Minh City - 098 6784 186
Email: sales@icdvietnam.com.vn
Zalo: Chat on Zalo now
References
- Collections Trust (UK), Monitoring temperature and humidity (accuracy by instrument type, salt check intervals) - collectionstrust.org.uk
- NPL (UK), Good Practice Guide No. 124, Humidity measurement (uncertainty, calibration intervals) - npl.co.uk
- Brown J.P., Hygrometric measurement in museums: calibration, accuracy, and the specification of relative humidity, Studies in Conservation 39 (1994) - doi.org
- BSS (Germany), Hygrometer im Test (test of 8 electronic and 6 dial hygrometers) - bss-schimmelpilz.de
- Greenspan L., Humidity Fixed Points of Binary Saturated Aqueous Solutions, J. Res. NBS 81A (1977) - pmc.ncbi.nlm.nih.gov
- Vaisala, Accuracy that lasts: an analysis of humidity sensor drift (2021) - vaisala.com
- NPS, Conserve O Gram 3/3: Comparing Temperature and Relative Humidity Dataloggers for Museum Monitoring - nps.gov
- Zdankiewicz E.M., A Comparison of Relative Humidity Sensing Technologies (UC Davis) - pasternack.ucdavis.edu
- Lawrence M.G., The Relationship between Relative Humidity and the Dewpoint Temperature in Moist Air, BAMS 86 (2005) - journals.ametsoc.org
- IPC/JEDEC J-STD-033C, Handling, Packing, Shipping and Use of Moisture/Reflow Sensitive SMDs - jedec.org
- DESCO Industries, Humidity Indicator Cards (how to read, 8-hour color change) - descoindustries.com
- US EPA, Mold Course Chapter 2: Why and Where Mold Grows (indoor humidity, hygrometer price) - epa.gov
